Zetastar Building One / Jordan Sherlansky / 18 Feb 2019
Facility Condition Assessment TemplateConducted on18th Feb, 2019BySafetyCulture Staff
Failed items
0
Created actions
0
Site
Sydney
Client / Site
Zetastar Building One
Conducted on

18th Feb, 2019

10:48 AM +08

Prepared by
Jordan Sherlansky
Inspection
Item status guide: 5 Excellent - Brand new and no issues to report - Plan for 8 to 10 year span 4 Good - No immediate issues or concerns - Consider replacement in 6 to 8 years 3 Fair - Average wear for building age. Not new but no immediate issues. - Replace within 5 to 6 years 2 Poor - Worn from use. Nearing end of expected life cycle. - Replace within 2 to 4 years 1 Critical - Extremely worn or damaged - Replace within the next 2 years
Sitework
Roads
2 - Poor
Notes
Cracked asphalt starting from main parking entrance.
Photos
Parking
2 - Poor
Notes
Further road damage from the main entrance leading to the parking area.
Photos
Pavement
2 - Poor
Signage
4 - Good
Fencing
3 - Fair
Irrigation
4 - Good
Stormwater drainage
4 - Good
Sewerage
4 - Good
Erosion control
4 - Good
Landscaping
5 - Excellent
Building Structure
Foundations
3 - Fair
Notes
Minor settlement cracks were observed in various locations in the foundation walls. This implies that some structural movement of the building has occurred. Cracks of this type should be watched for any sign of additional movement. In the absence of any sign of ongoing movement, repair should not be necessary.
Photos
Walls
3 - Fair
Notes
Common minor cracks were observed on the exterior walls of the building in various locations. This implies that structural movement has occurred. The location, size, shape of these cracks is common. The inspection did not find evidence of significant movement requiring immediate major repairs.
Columns
4 - Good
Beams
4 - Good
Slabs
4 - Good
Building Interior
Furniture
4 - Good
Appliances
4 - Good
Floors
3 - Fair
Notes
Minor unevenness was observed in the floor structure in various locations. This condition is common. It may be the result of the materials, framing design, installation methods and aging of the building. There was no evidence or need for immediate, costly repair.
Floor finishes
4 - Good
Walls
3 - Fair
Notes
Minor hairline cracks in interior walls. No immediate repairs needed.
Photos
Wall finishes
3 - Fair
Notes
No problems aside from minor, normal hairline cracks.
Ceilings
4 - Good
Casework (cabinets, bookcases, nightstands)
4 - Good
Fixtures
4 - Good
Doors
4 - Good
Hardware (bolts, nails, screws, hinges, locks, bolts, latches)
4 - Good
Building Exterior
Roofing structures
3 - Fair
Notes
The installation of the chimney flashing is incomplete and should be repaired to avoid leaks. Aluminum should not be used on chimney flashing because aluminum reacts with the lime in the mortar. The flashing should be galvanized steel embedded in the chimney and installed counter flashing to the roof line over step flashing. Have this evaluated by a tinsmith.
Photos
Balconies
4 - Good
Breezeways
4 - Good
Stairs
4 - Good
Exterior walls
4 - Good
Exterior windows.
4 - Good
Mechanical Systems
Heating, ventilation and air conditioning (HVAC) systems
4 - Good
Electrical Systems
Electrical wiring
3 - Fair
Notes
Wiring in the basement should not touch hot air ductwork or hot water piping.
Photos
Sockets
4 - Good
Lighting
4 - Good
Emergency generators.
4 - Good
Plumbing
Piping
2 - Poor
Notes
Corrosion on the exterior of the supply piping was observed.
Photos
Water pressure
4 - Good
Toilets
2 - Poor
Notes
The toilet tank is loose in the second floor bathroom. Recommend securing to the bowl and replace gasket as needed.
Photos
Plumbing fixtures
4 - Good
Vertical Transportation
Escalators
4 - Good
Passenger elevators
4 - Good
Freight elevators
4 - Good
Health and Fire Safety
Air quality
4 - Good
Water quality
4 - Good
Fire alarms
4 - Good
Fire suppression systems
4 - Good
Compliance with Building Codes & Regulations
The facility complies with the International Building Code (IBC)
Yes
The facility complies with the International Residential Code (IRC)
Yes
The facility complies with the International Existing Building Code (IEBC)
Yes
Name and Signature of inspector
Jordan Sherlansky
18th Feb, 2019 11:46 AM +08
Photos